126kv/1250A Oip Condenser Transformer Bushing (draw lead)
Click image to view full size image
Product: Views:227126kv/1250A Oip Condenser Transformer Bushing (draw lead) 
Unit price: Negotiable
MOQ:
Quantity:
Delivery date: Since the payment date Days delivery
Valid until: Long-term effective
Last updated: 2017-07-22 07:22
  Inquiry
Details
Main properties
electric properties 
System nominal voltage Un(Kv) 35 66 110 132 150 220
Rated voltage Ur(Kv) 40.5 72.5 126 145 170 252
60s power frequency withstand voltage: Dry kv 95 147 230 275 325 460
Wet Kv 80 140 230 275 325 460
Lightning impulse withstand voltage chopped wave Full wave Kv(peak) 200 325 550 650 750 1050
Kv(peak)   375 635 750 865 1210
Operating impulse withstand voltage(dry or wet)           850
dielectric dissipation factor tanδ (20ºC temperature)Max. Ur:0.004
increment 1.05Ur/√3-Ur:0.0005
Ur Partial discharge under voltage ≤5pC
1.5Ur Partial discharge under voltage ≤10pC
 
Bending testing load
Rated voltage Ur(Kv) Bending testing load(N)
Rated current Ir(A)
≤800 800-1600 1600-2500 ≥3150
≤52 1250 2000 2000 2500
72.5 1250 1250 4000 4000
126-170 3150 4000 4000 4000
252 4000 5000 5000 5000
 
other properties
Item# Testing performance index
1 The bushing can withstand the gauge pressure of the sealing test at 0.2MPa  no leakage
2 interior tranformer oil Pressure value(Kv) ≥55
Dielectric loss factor tanδ(90ºC) ≤0.004
Mico water(μg/g) ≤10
Chromatography Acetylene(μL/L) 0
Hydrogen(μL/L) ≤30
Total hydrocarbons(μL/L) ≤9
3 Measurement of Dielectric Loss Factor of Terminal to earth under 2kV voltage ≤0.02
 
Type designation
BRDLW- (rated voltage:kV)/ (rated current:A)- (Antifouling grade)
BR-OIP Condenser transformer bushing,OIP Condenser wall bushing represent as CR
D-Short tail bushing,if no "D" it should be Medium-short tail bushing
L:can install CT
W:Antifouling type,3 means creepage distance is 25mm/kV,4 means creepage distance is 31mm/Kv

Technical parameters:
126kV/1250A OIP Condenser transformer bushing(draw lead)
Code Type Rated voltage Kv Rated current A Main Dimensions(mm) Creepage distance MASS KG
L L1 L2 L3 L4 L5 D1 D2 D3 D d1 d2 d3 d4 A Z X
BR5234A BRDLW-126/1250-3 126 1250 2580 2285 1100 840 400 40 200 180 400 450 36 48 24 18 50 90 140 3150 170
BR5244A  BRDLW-126/1250-4 126 1250 2730 2435 1250 840 400 40 200 180 400 450 36 48 24 18 50 90 140 3906 191
BR5235A BRDLW-126/1250-3 126 1250 2730 2435 1100 990 550 40 200 180 400 450 36 48 24 18 50 90 140 3150 185
BR5245A BRDLW-126/1250-4 126 1250 2880 2585 1250 990 550 40 200 180 400 450 36 48 24 18 50 90 140 3906 205
BR5243A BRDLW-126/1250-3 126 1250 2630 2335 1250 740 300 40 200 180 400 450 36 48 24 18 50 90 140 3906 188

Other HV bushing reference:






 