Main properties | |||||||
electric properties | |||||||
System nominal voltage Un(Kv) | 35 | 66 | 110 | 132 | 150 | 220 | |
Rated voltage Ur(Kv) | 40.5 | 72.5 | 126 | 145 | 170 | 252 | |
60s power frequency withstand voltage: | Dry kv | 95 | 147 | 230 | 275 | 325 | 460 |
Wet Kv | 80 | 140 | 230 | 275 | 325 | 460 | |
Lightning impulse withstand voltage chopped wave | Full wave Kv(peak) | 200 | 325 | 550 | 650 | 750 | 1050 |
Kv(peak) | 375 | 635 | 750 | 865 | 1210 | ||
Operating impulse withstand voltage(dry or wet) | 850 | ||||||
dielectric dissipation factor tanδ | (20ºC temperature)Max. | Ur:0.004 | |||||
increment | 1.05Ur/√3-Ur:0.0005 | ||||||
Ur Partial discharge under voltage | ≤5pC | ||||||
1.5Ur Partial discharge under voltage | ≤10pC |
Bending testing load | ||||
Rated voltage Ur(Kv) | Bending testing load(N) | |||
Rated current Ir(A) | ||||
≤800 | 800-1600 | 1600-2500 | ≥3150 | |
≤52 | 1250 | 2000 | 2000 | 2500 |
72.5 | 1250 | 1250 | 4000 | 4000 |
126-170 | 3150 | 4000 | 4000 | 4000 |
252 | 4000 | 5000 | 5000 | 5000 |
other properties | ||||
Item# | Testing | performance index | ||
1 | The bushing can withstand the gauge pressure of the sealing test at 0.2MPa | no leakage | ||
2 | interior tranformer oil | Pressure value(Kv) | ≥55 | |
Dielectric loss factor tanδ(90ºC) | ≤0.004 | |||
Mico water(μg/g) | ≤10 | |||
Chromatography | Acetylene(μL/L) | 0 | ||
Hydrogen(μL/L) | ≤30 | |||
Total hydrocarbons(μL/L) | ≤9 | |||
3 | Measurement of Dielectric Loss Factor of Terminal to earth under 2kV voltage | ≤0.02 |
Type designation | ||||||||
BRDLW- (rated voltage:kV)/ (rated current:A)- (Antifouling grade) | ||||||||
BR-OIP Condenser transformer bushing,OIP Condenser wall bushing represent as CR | ||||||||
D-Short tail bushing,if no "D" it should be Medium-short tail bushing | ||||||||
L:can install CT | ||||||||
W:Antifouling type,3 means creepage distance is 25mm/kV,4 means creepage distance is 31mm/Kv |
Technical parameters:
40.5kV high current OIP condenser transformer bushing | ||||||
Code | Type | Rated voltage kV | Rated current | Creepage distance | Cantilever strength | Mass kg |
BR3B40 | BRW-40.5/25000-4 | 40.5 | 25000 | 1300 | ≥4000N | 585 |
BR3B42 | BRLW-40.5/25000-4 | 40.5 | 25000 | 1300 | ≥4000N | 650 |
BR3A40 | BRW-40.5/16000-4 | 40.5 | 16000 | 1300 | ≥4000N | 230 |
BR3A43 | BRLW-40.5/16000-4 | 40.5 | 16000 | 1300 | ≥4000N | 265 |
Code | L | L1 | L2 | L3 | Outer termianl | Oil end terminal | Flange | D1 | D2 | |||||||||||||||
m1 | n1 | d1 | A1 | L4 | L5 | m2 | n2 | d2 | A2 | L6 | L7 | n3 | d3 | D3 | D | H | h | |||||||
BR3B42 | 1175 | 450 | 410 | 30 | 4 | 18 | 14 | 40 | 300 | 155 | 2 | 12 | M12 | 50 | 300 | 100 | 16 | 22 | 620 | 680 | 85 | 25 | 610 | 490 |
BR3B40 | 1345 | 450 | 580 | 200 | 4 | 18 | 14 | 40 | 300 | 155 | 2 | 12 | M12 | 50 | 300 | 100 | 16 | 22 | 620 | 680 | 85 | 25 | 610 | 490 |
BR3A40 | 1200 | 450 | 430 | 30 | 4 | 12 | 14 | 40 | 235 | 150 | 2 | 6 | M12 | 40 | 130 | 120 | 8 | 22 | 430 | 480 | 85 | 25 | 480 | 355 |
BR3A43 | 1470 | 450 | 700 | 300 | 4 | 12 | 14 | 40 | 235 | 150 | 2 | 6 | M12 | 40 | 130 | 120 | 8 | 22 | 430 | 480 | 85 | 25 | 480 | 355 |